Main features
| Rated prime power (PRP) | : | 74 kW | | Voltage | : | 480, 277 V | | Voltage | : | 208, 120 V | | Voltage | : | 240, 120 V | | Frequency | : | 60 Hz | | Engine manufacturer | : | Perkins | | Fuel | : | Diesel | | Speed governor | : | Electronic |
GSW Series - Perkins
The GSW Series provides the most professional way to fulfill power requirements with highest reliability and excellent performance.
|
| Rated prime power (PRP) | 74 kW | | | 93 kVA | | Emer Power (LTP) | 82 kW | | | 103 kVA | | Voltage | 480, 277 V | | Frequency | 60 Hz | | Power factor | 0,8 cosPhi |
|
| Rated prime power (PRP) | 74 kW | | | 92 kVA | | Emer Power (LTP) | 82 kW | | | 102 kVA | | Voltage | 208, 120 V | | Frequency | 60 Hz | | Power factor | 0,8 cosPhi |
|
| Rated prime power (PRP) | 68 kW | | | 68 kVA | | Emer Power (LTP) | 74 kW | | | 74 kVA | | Voltage | 240, 120 V | | Frequency | 60 Hz | | Power factor | 1 cosPhi |
|
| Engine manufacturer | Perkins | | Model | 1104D-E44TAG1 | | Fuel | Diesel | | Exhaust emission | EPA Tier 3 | | Cooling system | Water | | Nominal operating speed | 1800 rpm | | Displacement | 269,1 cu inches | | Number of cylinders and disposition | 4, inline | | Air intake | Turbo intercooler | | Power (PRP) | 110 bhp | | Power (LTP) | 122 bhp | | Fuel consumption (III) at 75% PRP | 4,31 gal/h | | Fuel consumption (III) at 100% PRP | 5,81 gal/h | | Specific fuel consumption at PRP | 0,363 lb/hph | | Speed governor | Electronic |
|
| Alternator specifications |
| Alternator manufacturer | Stamford | | Model | UCI 274 C | | Power at 27°C (480 V) | 106 kWE | | | 133 kVA | | Power at 27°C (208 V) | 93 kWE | | | 116 kVA | | Power at 27°C (240 V) | 54 kWE | | | 68 kVA | | Insulation class | H | | Protection grade | IP 23 | | Voltage regulation system | Electronic, 1,5% |
|
| Fuel tank capacity | 91,93 gal | | Autonomy (III) at 75% PRP | 21,3 h | | Autonomy (III) at 100% PRP | 16 h |
|
| Length | 106,69 in | | Width | 46,50 in | | Height | 60,39 in | | Dry weight | 3.280,47 lb |
|
| Automatic control panel (ACP) |
| Description | Automatic control panel mounted on the genset, complete with digital control unit AC01 for monitoring, control and protection of the generating set. |
|
| Automatic control panel (ACP): digital instrumentation |
| Generator set voltage (3 phases) | Yes | | Mains voltage | Yes | | Generator set frequency | Yes | | Generator set current (3 phases) | Yes | | Battery voltage | Yes | | Power (kW - kVA - kVAr) | Yes | | Power factor | Yes | | Hour counter | Yes | | Engine rpm | Yes | | Fuel level (%) | Yes | | Engine temperature | Yes |
|
| Automatic control panel (ACP): commands and other features |
| Setting: Automatic test | Yes | | Setting: Automatic starting | Yes | | Setting: Engine locked | Yes | | Setting: Mains contactor forced | Yes | | Setting: Manual start | Yes | | Setting: Genset contactor forced | Yes | | Emergency stop button | Yes | | Remote start capable | Yes | | Acoustic alarm | Yes | | Integrated battery charger | Yes |
|
| Automatic control panel (ACP): protections with alarm |
| Engine protection: low fuel level | Yes | | Engine protection: low oil pressure | Yes | | Engine protection: high engine temperature | Yes | | Genset protection: start failure | Yes | | Genset protection: under/over voltage | Yes | | Genset protection: under/over frequency | Yes | | Genset protection: under/over battery voltage | Yes | | Genset protection: battery charge failure | Yes | | Genset protection: overload | Yes |
|
| Automatic control panel (ACP): protections with shutdown |
| Circuit bracker and differential protection | Optional | | Engine protection: low fuel level | Yes | | Engine protection: high engine temperature | Yes | | Engine protection: low oil pressure | Yes | | Genset protection: under/over voltage | Yes | | Genset protection: overload | Yes | | Genset protection: under/over battery voltage | Yes | | Genset protection: battery charge failure | Yes |
|
| Automatic control panel (ACP): output features |
| Power cable connected to terminals board (external) | Yes | | Main lugs | Yes |
|
| Genset supplements (some available from factory only) |
| PMG for Stamford alternator + MX321 AVR | Optional | | Automatic fuel transfer pump | Optional | | Different color canopy | Optional | | Engine electronic governor | Optional | | Engine preheat system | Optional | | Remote control by GSM | Optional | | Galvanized skids frame (Heavy duty galvanized skid to be installed under the genset. Easily transportable with fork lift) | Optional | | Extended capacity sub-base fuel tank | Optional | | Road trailer | Optional | | Automatic transfer switch | Optional |
|
Technical specifications are subject to change without notice. Consult your local PRAMAC representative for more information.
|
|