GSW330M (Alt. S)
Main Features
FREQUENCY
Hz
50
VOLTAGE
V
400
POWER FACTOR
cos ϕ
0.8
PHASE
3
Power Rating
EMERGENCY STANDBY POWER ESP
kVA
330.00
EMERGENCY STANDBY POWER ESP
kW
264.00
PRIME POWER PRP
kVA
306.47
PRIME POWER PRP
kW
245.18
Engine specifications
ENGINE BRAND
ENGINE BRAND
MTU
MODEL
MODEL
6R1600G20F
ENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM
Water
[50HZ] EXHAUST EMISSION LEVEL
[50HZ] EXHAUST EMISSION LEVEL
Stage IIIA
[60HZ] EXHAUST EMISSION OPTIMIZED FOR EPA TIER (EPA)
[60HZ] EXHAUST EMISSION OPTIMIZED FOR EPA TIER (EPA)
40 CFR 89 - Tier 3
Alternator Specifications
ALTERNATOR
Stamford
ALTERNATOR
Dimensional data
INSTALLATION DRAWING
2673
Extended Fuel Tank
INSTALLATION DRAWING FOR EFT VERSION EXTENDED FUEL TANK
2674
INSTALLATION DRAWING FOR EFT VERSION EXTENDED FUEL TANK
LTS - Load Transfer Switch [Accessories for ACP Automatic Control Panel]
LTS PANEL SIZE
LTS PANEL SIZE